By far the largest and most important component of any earthing or structural lightning protection system is the actual conductor.

Furse offer a comprehensive range of copper and aluminium conductors in each of the main world standard formats, ie flat tape, solid circular and stranded.

Conductor colour chart

The choice of a lightning protection conductor is usually governed by its aesthetic impact on the structure to be protected. For many people the term lightning conductor conjures up an image of a bright green strip running down the spire of a church. This would clearly be unacceptable to the owner/architect of a modern structure.

In order to reduce the impact of an external system Furse offer a range of UV stabilised PVC covered tapes and solid circular conductors (only 10mm diameter) in colours chosen to match common building materials.

Conductor ratings
 
Black 18B29
Green BS 6746C
Grey 00A07
Stone 08B23
White 10B15
Brown 06C39
For below ground earthing applications Furse produce a large range of bare copper, tape and stranded conductors thus offering the designer of the system the correctly rated conductor without the need to oversize.

The following conductor ratings are based upon the recommendations of
BS 7430 with an initial conductor temperature of 300C and a maximum temperature of 2500C.

Conductor
size
CSA kA for
1 sec
kA for
3 sec
Part no Conductor
size
CSA kA for
1 sec
kA for
3 sec
Part no
12.5 x 1.5mm 18.75 3.3 1.9 TC005 31 x 6mm 186 32.7 18.9 TC050
12.5 x 3mm 37.5 6.6 3.8 TC010 38 x 3mm 114 20.1 11.6 TC055
20 x 1.5mm 30 5.3 3.0 TC015 38 x 5mm 190 33.4 19.3 TC060
-FU
20 x 3mm 60 10.6 6.1 TC020 38 x 6mm 228 40.1 23.2 TC065
25 x 1.5mm 37.5 6.6 3.8 TC025 40 x 3mm 120 21.1 12.2 TC067
25 x 3mm 75 13.2 7.6 TC030 40 x 4mm 160 28.2 16.3 TC066
25 x 4mm 100 17.6 10.2 TC035 40 x 5mm 200 35.2 20.3 TC071
25 x 6mm 150 26.4 15.2 TC040 40 x 6mm 240 42.2 24.4 TC068
30 x 2mm 60 10.6 6.1 TC039 40 x 6.3mm 252 44.4 25.6 TC069
30 x 3mm 90 15.8 9.1 TC042 50 x 3mm 150 26.4 15.2 TC070
30 x 4mm 120 21.1 12.2 TC044 50 x 4mm 200 35.2 20.3 TC075
30 x 5mm 150 26.4 15.2 TC043 50 x 5mm 250 44.0 25.4 TC078
31 x 3mm 93 16.4 9.5 TC045 50 x 6mm 300 52.8 30.5 TC080
31.5 x 4mm 126 22.2 12.8 TC048 50 x 6.3mm 315 55.4 32.0 TC082